Alarms, Amplifiers, and Transmitters for Strain Gauge, Bridge, Pressure Transducer or Sensor, Load Cell Applications |
|||
---|---|---|---|
Click on PDF links below for product information |
Links Product brochure Options & accessories Regulatory compliance Reference Info Troubleshooting strain gauge sensors LoopTracker and Output Test Sink vs source Application Notes 6-Wire strain gauges Pressure sensor vs. pressure transmitter Pressure transducer calibration Weighing shipping containers Pressure system calibration Pressure transducer calibration Plastic extruder pressure Extrudung guitar strings Custom product for high speed pill presses |
How to select your product
|
Ready to order? Other ways to order
|
Model | Input/Output | Features | Product |
Alarm Trip for 1 to 4 Sensors:
APD 1500 from $379 |
Specify Strain gauge mV/V rating, mV range, Excitation voltage Factory configured 100 Ω to 10000 Ω strain gauge 5 mV to 2000 mV 1-10 VDC excitation Accepts one sensor for input APD 1500 Single Alarm Trip Dual SPDT contact sets Standard: HI alarm, non-latching, normal acting See data sheet for alarm options APD 1520 Dual Alarm Trip 2 independent SPDT contact sets Standard: HI/LO alarms, non-latching, normal acting See data sheet for alarm options |
|
APD 1500, APD 1520 |
Isolated DC Amplifier for One Sensor:
API 4051 G I from $359Open Datasheet Download Datasheet |
Specify input range Factory configured One 350 Ω stain gauge, load cell or bridge sensor 1 mV to 2000 mV Accepts one sensor for input Specify excitation voltage 4 to 10 VDC Specify output range Factory configured 0-1 V to 0-10 V ±1 V to ±10 V 0-1 mA to 0-20 mA, 4-20 mA |
|
API 4051 GI |
Isolated DC Amplifier for One Sensor:
APD 4051 from $389Open Datasheet Download Datasheet |
Specify input range Factory Configured One 350 Ω stain gauge, load cell or bridge sensor 1 mV to 2000 mV Accepts one sensor for input Specify excitation voltage Factory Configured 4 to 10 VDC, 30 mA max. Specify output range Factory Configured 0-1 V to 0-10 V ±1 V to ±10 V 0-1 mA to 0-20 mA, 4-20 mA |
|
APD 4051 |
Non-Isolated DC Amplifier for 1 to 4 Sensors:
Field Selectable Minuteman SetupAPI 4058 G from $379Open Datasheet Download Datasheet Email Datasheet Link |
Field configurable Input 0-5 mVDC to 0-1200 mVDC Accepts one to four sensors for input Field settable excitation voltage 0-10 VDC in 1 VDC steps, 115 mA max. 18 Field configurable outputs 0-1 V to ±10 V 0-2 mA to 0-20 mA, 4-20 mA |
|
API 4058 G |
Non-Isolated DC Amplifier for 1 Sensor
Field Selectable Minuteman SetupAPD 4058 from $429Open Datasheet Download Datasheet Email Datasheet Link |
Field configurable 0-5 mVDC to 0-1200 mVDC Accepts one sensor for input Field settable excitation voltage 0-10 VDC in 1 VDC steps, 30 mA drives one sensor 18 field configurable outputs 0-1 V to ±10 V 0-2 mA to 0-20 mA, 4-20 mA |
|
APD 4058 |
Isolated DC Amplifier for 1 to 4 Sensors:
Field Selectable Minuteman SetupAPI 4059 G from $459Open Datasheet Download Datasheet Email Datasheet Link |
Field configurable 0-5 mVDC to 0-400 mVDC, 120 mA Accepts one to four sensors for input Field settable excitation voltage 0-10 VDC in 1 VDC steps 18 field configurable outputs 0-1 V to ±10 V 0-2 mA to 0-20 mA, 4-20 mA Zero Offset (Tare) ±100% of span in 15% increments |
|
API 4059 G Socket sold separately |
Isolated DC Amplifier for 1 to 4 Sensors:
Field Selectable Minuteman SetupAPD 4059 from $469Open Datasheet Download Datasheet Email Datasheet Link |
Field configurable 0-5 mVDC to 0-400 mVDC Field settable excitation voltage 0-10 VDC in 1 VDC steps, 120 mA Accepts one to four sensors for input 18 field configurable outputs 0-1 V to ±10 V 0-2 mA to 0-20 mA, 4-20 mA |
|
APD 4059 |
Isolated DC Amplifier for 1 to 4 Sensors with
|
Field configurable input 0-5 mVDC to 0-400 mVDC Field settable excitation voltage 0-10 VDC in 1 VDC steps, 120 mA Use internal or external calibration resistor Specify calibration resistor value if required Accepts one to four sensors for input 18 field configurable outputs 0-1 V to ±10 V 0-2 mA to 0-20 mA, 4-20 mA Zero Offset (Tare) ±100% of span in 15% increments |
|
APD 4059CR |
IsoSplitter® Strain Gauge Amplifier/Signal Splitter |
Specify input range Factory configured for one 350 Ω (or greater) strain gauge, pressure transducer, pressure sensor, load cell, or bridge Strain gauge mV range: 1 mV to 2000 mV Specify mV/V or mV range mV/V sensitivity X excitation voltage = total mV range Specify excitation voltage 4 to 10 VDC excitation at 30 mA Specify output range for each channel 2 independent channels 0-1 V to 0-20 V ±1 V to ±10 V 0-1 mA to 0-25 mA, 4-20 mA |
|
APD 5393 Strain Gauge IsoSplitter |
DuoPak® 2 Channel Isolated Signal ConditionersChoose Your Factory Configuration APD 2000 Series from $629 |
Specify input range for each channel Accepts one sensor for each input channel APD 2005 Ch1: DC mV/V/mA Ch2: Strain gauge APD 2015 Ch1: RTD Ch2: Strain gauge APD 2035 Ch1: Potentiometer Ch2: Strain gauge APD 2055 Ch1: Strain gauge Ch2: Strain gauge APD 2056 Ch1: Strain gauge Ch2: AC mV/V/mA APD 2057 Ch1: Strain gauge Ch2: Frequency Specify output range for each channel 2 independent channels 0-1 V to 0-20 V ±1 V to ±10 V 0-1 mA to 0-25 mA, 4-20 mA |
|
APD 2000 Series Strain Gauge |
Strain Gauge/Load Cell/Bridge Input |
Field Configurable Input Input: One input channel connection for up to 4 (350 Ω) or 8 (1000 Ω) strain gauge load cells 4 or 6 wire Excitation supply Sensitivity: 1 to 64 mV/V Switch I/O for either tare or alarm Field Configurable Output Output: 4-20 mA, 0-20 mA 0-5 V, 0-10 V Modbus RTU requires backplane connector system Configure with EASY SETUP software and standard micro-USB cable 0.01% FS accuracy class 24 bit analog-digital conversion Upgradeable firmware Settable sampling rate Alarm with programmable hysteresis Configurable resolution Settable floating-point value Stabilized measurement with noise filter Download EASY SETUP software Download Z-series LabView drivers Download Z-SG2 DWG CAD file Download Z-SG2 3D STP CAD file |
|
Z-SG2 |
Strain Gauge/Load Cell/Bridge Input |
Field Configurable Input Input: One input channel connection for up to 4 (350 Ω) or 8 (1000 Ω) strain gauge load cells, 87 Ω minimum impedance 4 or 6 wire Use SG-EQ4 for easy wiring of mutiple load cells Excitation supply Sensitivity: 1 to 64 mV/V Switch I/O for either tare or alarm Field Configurable Output Output: 4-20 mA, 0-20 mA 0-5 V, 0-10 V Modbus RTU Configure with EASY SETUP software and standard micro-USB cable 0.01% FS accuracy class 24 bit analog-digital conversion Upgradeable firmware Settable sampling rate Alarm with programmable hysteresis Configurable resolution Settable floating-point value Stabilized measurement with noise filter Download EASY SETUP software Download Z-series LabView drivers Download Z-SG3 3D STP CAD file |
|
Z-SG3 |
RS232/USB, TTL/USB, RS485/USB Isolated Serial ConverterSeneca S117P-1 $299 *stock item*Open S117P-1 datasheet Download S117P-1 datasheet Open S117P-1 installation Download S117P-1 installation S117P-1 SoftwareDownload S117P-1 Software |
Programming kit for T120 T121 Z-SG |
Includes Converter box Software mini CD (or download latest) Adapter cable |
S117P1 |
Load Cell, Strain Gauge, Bridge |
Input Up to 4 strain gauges Output Summed signal from up to 4 strain gauges |
|
SG-EQ4 SG-EQ4-BOXPG7 |
Z-Series Backplane ConnectorZ-PC-DINAL1-35 $40Open Z-PC-DIN datasheet Download Z-PC-DIN datasheet Open Z-PC-DIN overview Download Z-PC-DIN overview |
Head terminal + 1 slot For one 17.5mm or one 35mm wide Z-PC module Connect power Connect Modbus Required for Modbus connection |
DIN rail mount with screw terminals, 1 slot Connect one 17.5 or 35mm Z-PC series module |
Z-PC-DINAL1-35 |
Z-Series Backplane ConnectorZ-PC-DINAL2-17.5 $45 *stock item*Open Z-PC-Z-PC-DIN datasheet Download Z-PC-DIN datasheet Open Z-PC-DIN overview Download Z-PC-DIN overview |
Head terminal + 2 slots For one or two 17.5mm wide Z-PC modules Connect power Connect Modbus Required for Modbus connection |
DIN rail mount with screw terminals, 2 slots Connect one or two 17.5mm Z-PC series modules |
Z-PC-DINAL2-17.5 |
Z-Series Backplane ExtenderZ-PC-DIN2-17.5 $45 *stock item*Open Z-PC-DIN datasheet Download Z-PC-DIN datasheet Open Z-PC-DIN overview Download Z-PC-DIN overview |
2 slot extension terminal For one or two 17.5mm wide Z-PC modules Connect power Connect Modbus Required for Modbus connection |
DIN rail mount with 2 slots Add one or two 17.5mm Z-PC series modules |
Z-PC-DIN2-17.5 |
4 Digit 4-20 mA Loop Powered DisplayField RangeableS315 $150 *stock item* |
Loop Powered Display Input: 4-20 mA Display: 4 digit red LED |
|
S315 |